Schneider Electric PM5100 Marine Instruments User Manual


 
PowerLogic™ PM5100 series user guide Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved 57
Setting Up Unary Alarms
To set up unary alarms:
Viewing Alarm Activity and History
There are two types of alarm entries: primary and secondary. The primary entry identifies
the alarm. The secondary entries provide pickup and dropout information.
The active alarm list holds 40 entries at a time. The list works as a circular buffer,
replacing old entries as new entries over 40 are entered into the alarm event queue. The
information in the alarm event queue reinitializes when the power meter resets.
The alarm history log holds 40 entries. The log also works as a circular buffer, replacing
old entries with new entries. This information is nonvolatile.
1. Press Unary. The unary alarm
Select screen appears.
2. Press
and to scroll
through the list of unary alarms.
3. Press Edit to select an alarm to
be configured.
4. Press Edit to select Enable.
5. Press + and - to scroll between
Yes and No.
6. Press OK to enable or disable
the alarm.
7. Press
to select Priority.
8. Press + and - to scroll through
priority options Low, None,
High, or Medium.
NOTE: See “Alarm Priorities”
on page 53 for more
information.
9. Press OK to set the priority.
10. Press
to save all alarms
selections and return to the
previous screen.
11. Press
to save all unary
alarm selections.