Schneider Electric PM870 Marine Instruments User Manual


 
© 2011 Schneider Electric. All Rights Reserved.
PowerLogic
TM
Series 800 Power Meter 63230-500-225A2
Chapter 3—Operation 3/2011
14
TIME Setup
LANG (Language) Setup
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until TIME is visible.
3. Press TIME.
4. Enter the HOUR.
5. Press OK.
6. Enter the MIN (minutes).
7. Press OK.
8. Enter the SEC (seconds).
9. Press OK.
10. Select how the time is displayed: 24H or
AM/PM.
11. Press OK to return to the SETUP MODE
screen.
12. Press
1; to return to the main screen.
13. To verify the new settings, press MAINT >
DIAG > CLOCK.
NOTE: The clock in the PM810 is volatile. Each time the meter resets, the PM810 returns
to the default clock date/time of 12:00 AM 01-01-1980. See “Date and Time Settings” on
page 69 for more information. All other PM800 Series meters have a non-volatile clock,
which maintains the current date and time when the meter is reset.

4)-%3%450
 /+



-).
3DB
(
(NTQ
PLSD110227
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until LANG is visible.
3. Press LANG.
4. Select the language: ENGL (English), FREN
(French), SPAN (Spanish), GERMN (German),
or RUSSN (Russian).
5. Press OK.
6. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
7. Press YES to save the changes.

,!.'5!'%

%.',
/+
PLSD110103