Schneider Electric PM870 Marine Instruments User Manual


 
PowerLogic
TM
Series 800 Power Meter 63230-500-225A2
Appendix A—Instrument Transformer Wiring: Troubleshooting Tables 3/2011
© 2011 Schneider Electric All Rights Reserved
74
Section I: Common Problems for 3-Wire and 4-Wire Systems
Section I—Case A
Symptoms: 3-Wire and 4-Wire Possible Causes
Zero amps
Zero kW, kVAR, kVA
CT secondaries shorted.
Less than 2% load on power meter based on CT ratio.
Example: with 100/5 CT's, at least 2A must flow through CT window for power
meter to “wake up.”
Section I—Case B
Symptoms: 3-Wire and 4-Wire Possible Causes
Negative kW of expected magnitude
Positive kVAR
Normal lagging power factor
All three CT polarities backwards; could be CTs are physically mounted
with primary polarity mark toward the load instead of toward source or
secondary leads swapped.
All three PT polarities backwards; again, could be on primary or secondary.
NOTE: Experience shows CTs are usually the problem.
Section I—Case C
Symptoms: 3-Wire and 4-Wire Possible Causes
Frequency is an abnormal value; may or may
not be a multiple of 50/60 Hz.
PTs primary and/or secondary neutral common not grounded (values as
high as 275 Hz and as low as 10 Hz have been seen).
System grounding problem at the power distribution transformer (such as
utility transformer), though this is not likely.