3/2011 Chapter 6—Alarms
55
Alarm Conditions and Alarm Numbers
This section lists the power meter’s predefined alarm conditions. For each alarm condition,
the following information is provided.
• Alarm No.—a position number indicating where an alarm falls in the list.
• Alarm Description—a brief description of the alarm condition
• Abbreviated Display Name—an abbreviated name that describes the alarm condition,
but is limited to 15 characters that fit in the window of the power meter’s display.
• Test Register—the register number that contains the value (where applicable) that is
used as the basis for a comparison to alarm pickup and dropout settings.
• Units—the unit that applies to the pickup and dropout settings.
• Scale Group—the scale group that applies to the test register’s metering value (A–F).
For a description of scale groups, see “Scale Factors” on page 49.
• Alarm Type—a reference to a definition that provides details on the operation and
configuration of the alarm. For a description of advanced alarm types, refer to
Table 6–9.
Table 6–8 lists the preconfigured alarms by alarm number.
NOTE: Current sag and swell alarms are enabled using PowerLogic software or by setting
up custom alarms. To do this, delete any of the above default disturbance alarms, and then
create a new current sag or swell alarm (see the example under the “Advanced Alarm
Groups” on page 53.). Sag and swell alarms are available for all channels.
Table 6–8: List of Default Disturbance Alarms by Alarm Number
Alarm
Number
Alarm Description
Abbreviated
Display Name
Test
Register
Units
Scale
Group
➀
Alarm
Type
➁
Disturbance Monitoring (1/2 Cycle) (PM870)
41 Voltage Swell A Swell Van Volts D 080
42 Voltage Swell B Swell Vbn Volts D 080
43 Voltage Swell C Swell Vcn Volts D 080
44 Voltage Swell A–B Swell Vab Volts D 080
45 Voltage Swell B–C Swell Vbc Volts D 080
46 Voltage Swell C–A Swell Vca Volts D 080
47 Voltage Sag A–N Sag Van Volts D 080
48 Voltage Sag B–N Sag Vbn Volts D 080
49 Voltage Sag C–N Sag Vcn Volts D 080
50 Voltage Sag A–B Sag Vab Volts D 080
51 Voltage Sag B–C Sag Vbc Volts D 080
52 Voltage Sag C–A Sag Vca Volts D 080
➀ Scale groups are described in Table 6–2 on page 49.
➁ Advanced Alarm types are described in Table 6–9 on page 56.