63230-500-225A2 PowerLogic
TM
Series 800 Power Meter
3/2011 Chapter 6—Alarms
51
Table 6–5: List of Default Basic Alarms by Alarm Number
Alarm
Number
Alarm Description
Abbreviated
Display Name
Test
Register
Units
Scale
Group
➀
Alarm
Type
➁
Standard Speed Alarms (1 Second)
01 Over Current Phase A Over Ia 1100 Amperes A 010
02 Over Current Phase B Over Ib 1101 Amperes A 010
03 Over Current Phase C Over Ic 1102 Amperes A 010
04 Over Current Neutral Over In 1103 Amperes B 010
05 Current Unbalance, Max I Unbal Max 1110 Tenths % — 010
06 Current Loss Current Loss 3262 Amperes A 053
07 Over Voltage Phase A–N Over Van 1124 Volts D 010
08 Over Voltage Phase B–N Over Vbn 1125 Volts D 010
09 Over Voltage Phase C–N Over Vcn 1126 Volts D 010
10 Over Voltage Phase A–B Over Vab 1120 Volts D 010
11 Over Voltage Phase B–C Over Vbc 1121 Volts D 010
12 Over Voltage Phase C–A Over Vca 1122 Volts D 010
13 Under Voltage Phase A Under Van 1124 Volts D 020
14 Under Voltage Phase B Under Vbn 1125 Volts D 020
15 Under Voltage Phase C Under Vcn 1126 Volts D 020
16 Under Voltage Phase A–B Under Vab 1120 Volts D 020
17 Under Voltage Phase B–C Under Vbc 1121 Volts D 020
18 Under Voltage Phase C–A Under Vca 1122 Volts D 020
19 Voltage Unbalance L–N, Max V Unbal L-N Max 1136 Tenths % — 010
20 Voltage Unbalance L–L, Max V Unbal L-L Max 1132 Tenths % — 010
21
Voltage Loss (loss of A,B,C, but
not all)
Voltage Loss 3262 Volts D 052
22 Phase Reversal Phase Rev 3228 — — 051
23 Over kW Demand Over kW Dmd 2151 kW F 011
24 Lagging true power factor Lag True PF 1163 Thousandths — 055
25 Over THD of Voltage Phase A–N Over THD Van 1207 Tenths % — 010
26 Over THD of Voltage Phase B–N Over THD Vbn 1208 Tenths % — 010
27 Over THD of Voltage Phase C–N Over THD Vcn 1209 Tenths % — 010
28 Over THD of Voltage Phase A–B Over THD Vab 1211 Tenths % — 010
29 Over THD of Voltage Phase B–C Over THD Vbc 1212 Tenths % — 010
30 Over THD of Voltage Phase C–A Over THD Vca 1213 Tenths % — 010
31 Over kVA Demand Over kVA Dmd 2181 kVA F 011
32 Over kW Total Over kW Total 1143 kW F 011
33 Over kVA Total Over kVA Total 1151 kVA F 011
34-40
Reserved for additional analog
alarms ➂
—————
34-40 Reserved for custom alarms. — — — — —
Digital
01
End of incremental energy
interval
End Inc Enr Int N/A — — 070
02 End of power demand interval End Dmd Int N/A — — 070
03 Power up/Reset Pwr Up/Reset N/A — — 070
04 Digital Input OFF/ON DIG IN S02 2 — — 060
05-12
Reserved for additional digital
alarms ➂
—————
05-12 Reserved for custom alarms — — — — —
➀ Scale groups are described in Table 6–2 on page 49 .
➁ Alarm types are described in Table 6–6 on page 52 .
➂ Additional analog and digital alarms require a corresponding I/O module to be installed.