Schneider Electric PM870 Marine Instruments User Manual


 
63230-500-225A2 PowerLogic
TM
Series 800 Power Meter
3/2011 Appendix A—Instrument Transformer Wiring: Troubleshooting Tables
© 2011 Schneider Electric All Rights Reserved
75
Section II: 3-Wire System Troubleshooting
Section II—Case A
Symptoms: 3-Wire Possible Causes
Currents and voltages approximately balanced
kW = near 0
kVAR = near 0
PF can be any value, probably fluctuating
CT secondary leads are swapped (A-phase lead on C-phase terminal and
vice versa).
PT secondary leads are swapped (A-phase lead on C-phase terminal and
vice versa).
Section II—Case B
Symptoms: 3-Wire Possible Causes
Phase B current is higher than A and C
(except in System Type 31).
kVA = about half of the expected magnitude
kW and kVAR can be positive or negative, less
than about half of the expected magnitude.
PF can be any value, probably a low leading
value.
One CT polarity is backwards.
3
Section II—Case C
Symptoms: 3-Wire Possible Causes
is higher than and
kVA = about half of the expected magnitude
kW and kVAR can be positive or negative, less
than about half of the expected magnitude
PF can be any value, probably a low leading
value
One PT polarity is backwards.
V
CA
3
V
AB
V
BC
Section II—Case D
Symptoms: 3-Wire Possible Causes
kW = 0 or low, with magnitude less than kVAR
kVAR = positive or negative with magnitude of
close to what is expected for kW
kVA = expected magnitude
PF = near 0 up to about 0.7 lead
Either the two voltage leads are swapped OR the two current leads are
swapped AND one instrument transformer has backwards polarity.
(look for high or phase B current = high)
The power meter is metering a purely capacitive load (this is unusual); in
this case kW and kVAR will be positive and PF will be near 0 lead.
V
CA
3=
3
Section II—Case E
Symptoms: 3-Wire Possible Causes
One phase current reads 0
kVA = about 1/2 of the expected value
kW, kVAR, and power factor can be positive or
negative of any value
The CT on the phase that reads 0 is short-circuited.
Less than 2% current (based on CT ratio) flowing through the CT on the
phase that reads 0.