Mitsubishi Electronics FR-D740-012 Marine Battery User Manual


 
127
Monitor display and monitor output signal
4
PARAMETERS
4.11 Monitor display and monitor output signal
4.11.1 Speed display and speed setting (Pr. 37)
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
* The maximum value of the setting range differs according to the Pr. 1 Maximum frequency, and it can be calculated from the following formula.
Note that the maximum setting value of Pr. 37 is 9998 if the result of the above formula exceeds 9998.
To display the machine speed, set in Pr. 37 the machine speed for 60Hz operation.
For example, when Pr. 37 = "1000", "1000" is displayed on the output frequency and set frequency monitor when the
running frequency is 60Hz. When running frequency is 30Hz, "500" is displayed.
∗1 Machine speed conversion formula .........Pr. 37 × frequency/60Hz
∗2 Hz is displayed in 0.01Hz increments and machine speed is in 0.001.
Purpose Parameter that should be Set
Refer to
Page
Display motor speed
Set speed
Speed display and speed setting Pr. 37
127
Change PU monitor display data
Monitor display/PU main display
data selection
Cumulative monitor clear
Pr. 52, Pr. 158, Pr. 170, Pr. 171,
Pr. 268, Pr. 563, Pr. 564, Pr. 891
128
Change the monitor output from
terminal AM
Terminal AM function selection Pr. 158
128
Set the reference of the monitor
output from terminal AM
Terminal AM standard setting Pr. 55, Pr. 56
133
Adjust terminal AM outputs Terminal AM calibration Pr. 901
134
The monitor display and frequency setting of the PU (FR-PU04/FR-PU07) can be changed to the machine speed.
Parameter
Number
Name
Initial
Value
Setting Range Description
37
Speed display
0
0 Frequency display, setting
0.01 to 9998 Machine speed at 60Hz.
Maximum setting value of Pr. 37 <
16777.215 × 60 (Hz)
Setting value of Pr. 1 (Hz)
Pr. 37 Setting
Output Frequency
Monitor
Set Frequency
Monitor
Frequency Setting Parameter Setting
0 (initial value) Hz Hz Hz
Hz
0.01 to 9998 Machine speed
∗1 Machine speed ∗1
Machine speed ∗1
NOTE
Under V/F control, the output frequency of the inverter is displayed in terms of synchronous speed, and therefore,
displayed value = actual speed + motor slip. The display changes to the actual speed (estimated value calculated
based on the motor slip) when slip compensation was made valid.
Refer to Pr. 52 when you want to change the PU main monitor (PU main display).
Since the panel display of the operation panel is 4 digits in length, the monitor value of more than "9999" is displayed as "----".
When the machine speed is displayed on the FR-PU04/FR-PU07, do not change the speed by using an up/down key in
the state where the set speed exceeding 65535 is displayed. The set speed may become arbitrary value.
While the machine speed is displayed on the monitor, values of other parameters related to speed (Pr. 1, etc.) are in
frequency increments. Set other parameters (Pr.1, etc.) related to speed in increments of frequency.
Due to the limitations on the resolution of the set frequency, the indication in the second decimal place may differ
from the setting.
CAUTION
Make sure that the running speed setting is correct.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Parameters referred to
Pr. 1 Maximum frequency Refer to page 83
Pr. 52 DU/PU main display data selection Refer to page 128