156
Frequency setting by analog input (terminal 2, 4)
(b) Method to adjust any point without application of a voltage (current) across terminals 2-5 (4-5)
(To change from 4V (80%) to 5V (100%))
Operation Display
1.
Confirm the RUN indication and operation mode
indication
The inverter should be at a stop.
The inverter should be in the PU operation mode.
(Use )
2. Press to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
3. Turn until appears.
4. Turn until appears.
5. Turn until ( ) appears.
Set to C4 Terminal 2 frequency setting gain.
Terminal 2 input is
selected
Terminal 4 input
is selected
6. Press to display the analog voltage
(current) value (%).
Analog voltage (current) value (%)
across terminals 2-5 (across
terminals 4-5)
7. Turn to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
The gain frequency is reached
when the analog voltage (current)
value across terminals 2-5 (across
terminals 4-5) is 100%.
8. Press to set.
Terminal 2 input
is selected
Terminal 4 input
is selected
Flicker...Parameter setting complete!!
(Adjustment completed)
Turn to read another parameter.
Press to return to the indication (step 4).
Press twice to show the next parameter ( ).
REMARKS
By pressing after step 6, you can confirm the current frequency setting bias/gain setting.
You can not check after performing operation in step 7.
C1 to C7 settings
are enabled.
REMARKS
The current setting at the instant of turning is
displayed.
You can not check after performing operation in step 7.
A