Mitsubishi Electronics FR-D740-012 Marine Battery User Manual


 
19
2
WIRING
Main circuit terminal specifications
(3) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table
below.
200V class
400V class
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.(Refer to page 83)
Pr. 72 PWM frequency
selection Setting
(carrier frequency)
008 014 025 042 070 or More
1 (1kHz) or less
200m
(656.19feet)
200m
(656.19feet)
300m
(984.25feet)
500m
(1640.42feet)
500m
(1640.42feet)
2 to15
(2kHz to 14.5kHz)
30m
(98.42feet)
100m
(328.08feet)
200m
(656.19feet)
300m
(984.25feet)
500m
(1640.42feet)
Pr. 72 PWM frequency
selection Setting
(carrier frequency)
012 022 036 050
080
or More
1 (1kHz) or less
200m
(656.19feet)
200m
(656.19feet)
300m
(984.25feet)
500m
(1640.42feet)
500m
(1640.42feet)
2 to15
(2kHz to 14.5kHz)
30m
(98.42feet)
100m
(328.08feet)
200m
(656.19feet)
300m
(984.25feet)
500m
(1640.42feet)
Total wiring length (FR-D720-070 or more, FR-D720S-070 or more,
FR-D740-080 or more)
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. (Refer to page 79 for Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection )
Refer to page 148 for details of Pr. 72 PWM frequency selection. Refer to the manual of the option for details of surge
voltage suppression filter (FR-ASF-H/FR-BMF-H).
When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (Pr. 162 = "1, 11"). (Refer to page 136)
500m
(1640.42feet)
or less
300m
(984.25feet)
300m
(984.25feet)
300m(984.25feet) + 300m(984.25feet)
= 600m(1968.50feet)
Motor capacity
(kW(HP))
0.1K(1/8) 0.2K(1/4) 0.4K(1/2) or more
Wiring length
20m (65.61feet) 50m (164.04feet) 100m (323.08feet)