Mitsubishi Electronics FR-A500 Marine Battery User Manual


 
- 19 -
1) Wiring the power supply and reactor 1
The cable size is dependent on the capacity of the high power factor converter. (Refer to page 17.)
Note: 1.Use the magnetic contactor (MC) and reactor 1 which match the high power factor converter capacity.
(Refer to page 62.)
2.Note that the FR-HCL01-55K is different in outline and terminal positions.
2) Wiring the reactor 1 and external box
Note: 1.The cable size is dependent on the capacity of the external box. (Refer to page 17.)
2.The reactor generates heat. When installing the reactor, exercise care not to heat the external box.
3.Run the cables to keep the reactor untouched by the sheaths of the cables.
Reactor 1
RS T
Power supply
RR2S S2TT2
NFB
MC
R
S
T
R2
S2
T2
Reactor 1
Power
supply
R
ST
Power
supply
FR-HCL01-55K appearance
(Note 2)
Reactor 1
Overall wiring distance: Within 10m
Resistor
R2 T2
S2
S3R3 T3
Terminal block
MC1.MC2
FR-HC
FR-HCL02
Resistor
Magnetic
contactor
Transtormer
Capacitor
Reactor 1 External box
R
S
T
R2
S2
T2
R2
S2
T2
R3
S3
T3