• Calibration procedure
(1) Connect a meter across converter terminals FM and SD. (Note
the polarity. FM is the positive terminal.)
(2) When a calibration resistor has already been connected, adjust
the resistance value to zero or remove the resistor.
(3) Set the required value in Pr. 54 “FM terminal function selection”.
Preset the parameter value as required by the output signal.
Display
1)
FR-PU02E
-1
PARAMETER UNIT
MONITOR
HELP
SET
EXT
O P
P U
O P
SHIFT
CLEAR
ACCEL DECEL THM
HIGH MID LOW
V/FMINMAX
BOOST
READ
WRITE STOP
REV
FWD
2)
2) 5)
4)
1) Press the [SET] key. . . . . . The parameter setting
mode is entered.
2) Type [9][0][0] and press
the [READ] key.
. . . . . The data as shown on
the right is displayed.
3) Input current is displayed.
4) Using the [ ] or [ ] key,
adjust the meter indicator
to a predetermined
position
. . . . . The meter indicator
moves. (It takes a long
time until the indicator
moves.)
5) Press the [WRITE] key. . . . . . Calibration is complete.
Press the [MONITOR] or [SET] key to
switch to the corresponding mode.
SETTING MODE
Set Pr. NO.
FOR PR. List
<HELP>
900 FM Tune
Run Inverter
set 60.00Hz
PU
901 AM Tune
Mntrl 2.31A
<WRITE>PU
900 FM Tune
Completed
<MONITOR>