York YK-ZCU4x0-0 Marine Sanitation System User Manual


 
System Manager/Zone Coordinator User’s Manual 63
428516-YUM-B-0908
3. Press the Setup button. The CV RTU Zone Setup screen appears.
4. Press the button for the zone parameter you want to change. The button label
describes the current setting. When you press the button, the appropriate screen
appears, allowing you to change the value. Table 16 lists these parameters and
their ranges or possible selections.
5. If you want to edit the name of the zone, press the Edit Zone Name button. On
the Zone Name screen that appears, use the on-screen keyboard to enter a new
name. Click OK to save.
6. After you complete the zone setup changes, press OK. The CV RTU Zone
Setup screen returns, reflecting the changes you made.
Table 16: CV RTU Zone Setup Parameters
Parameter Parameter Range/Selections
Thermostat Warm/Cool Adjust Enabled or Disabled
Temporary Occupancy Input Enabled or Disabled
Control Mode Auto, Heating, Cooling, Fan Only, Off
Heating Unocc Setpoint
Valid range 55.0 to 68.0 Deg F
1
1. Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied
Heating Occ Setpoint
Valid range 62.0 to 72.0 Deg F
1
Cooling Occ Setpoint
Valid range 68.0 to 78.0 Deg F
1
Cooling Unocc Setpoint
Valid range 75.0 to 90.0 Deg F
1
Figure 43: CV RTU Zone Setup Screen
CV RTU 24 - Zone Setup
Thermostat Warm / Cool
Adjust:
Temporary Occupancy
Input:
Control Mode:
FIG:ZneStupCVRTU
Enabled
Select value to modify.
Edit Zone Name
Heating Unocc Setpoint:
Heating Occ Setpoint:
Cooling Occ Setpoint:
Cooling Unocc Setpoint:
62.0 Deg F
Zone Status
Instant
Shutdown
Auto
Enabled
68.0 Deg F
72.0 Deg F
78.0 Deg F