Conduit 1. Seal the conduit threads with thread sealant (the transmitter conduit
seal interface was qualified using Grafoil™ tape). Conduit threads
mate with a standard
1
/2–14 NPT male fitting.
2. Starting at zero thread engagement, install the conduit into the
transmitter between 4 and 7 turns, or a minimum of 12.5 ft-lb (16.9
N-m). Hold the electronics housing securely to avoid damaging the
threaded neck seal between the sensor module and the electronics
housing during conduit installation.
3. Provide separate support for the conduit if necessary.