Rosemount 1153 Series D
6-8
Static Pressure and Overpressure Limits
Rosemount 1153DD:
0.5 psia to 2,000 psig (3.4 kPa abs to 13.8 MPa) maximum rated static
pressure for operation within specifications; overpressure limit is 2,000
psig (13.8 MPa) on either side without damage to the transmitter
Rosemount 1153HD:
0.5 psia to 3,000 psig (3.4 kPa abs to 20.7 MPa) maximum rated static
pressure for operation within specifications; overpressure limit is 3,000
psig (20.7 MPa) on either side without damage to the transmitter
Overpressure Limits
Rosemount 1153GD and Rosemount 1153AD:
Operates within specifications from 0.5 psia (3.4 kPa abs) to upper range
limit. Overpressure limits without damage to the transmitter are:
PHYSICAL
SPECIFICATIONS
Materials of Construction
Isolating Diaphragms:
316L SST
Drain/Vent Valves:
316 SST
Process Flanges:
CF-8M (cast version of 316 SST)
Process O-rings:
316L SST
Electronics Housing O-rings:
Ethylene propylene
Fill Fluid:
Silicone oil
Flange Bolts and Nuts:
Plated alloy steel, per ASTM A-540
Electronics Housing:
316 SST
Mounting Bracket:
316L SST
Mounting Bolts (Bracket to Transmitter):
SAE J429 Carbon steel, Grade 2 or Grade 5
Range Code Overpressure Limit
3–8 2,000 psig (13.8 MPa)
9 4,500 psig (31.0 MPa)
0 6,000 psig (41.34 MPa)