INVERTER SETTING
4
Pr. 340
Setting
Pr. 79
Setting
Operation Mode at Power ON or Power
Restoration
Operation Mode Switchover
0
(initial
value)
0 (initial
value)
External operation mode
Switching among the External, PU, and NET operation mode is
enabled
*1
1 PU operation mode PU operation mode fixed
2 External operation mode
Switching between the external and NET operation mode is enabled
Switching to the PU operation mode is disallowed
3, 4 External/PU combined operation mode Operation mode switching is disallowed
6 External operation mode
Switching among the External, PU, and NET operation mode is
enabled while running.
7
X12 (MRS) signal ON
..... External operation mode
Switching among the External, PU, and NET operation mode is enabled
*1
X12 (MRS) signal OFF
... External operation mode
External operation mode fixed (Forcibly switched to external
operation mode.)
1
0 NET operation mode
Same as when Pr. 340 = "0"
1 PU operation mode
2
NET operation mode
3, 4 External/PU combined operation mode
6
*3 NET operation mode
7
X12 (MRS) signal ON.... NET operation mode
X12 (MRS) signal OFF
... External operation mode
10
0 NET operation mode Switching between the PU and NET operation mode is enabled *2
1 PU operation mode Same as when Pr. 340 = "0"
2
NET operation mode NET operation mode fixed
3, 4 External/PU combined operation mode Same as when Pr. 340 = "0"
6
*3 NET operation mode
Switching between the PU and NET operation mode is enabled while
running
*2
7 External operation mode Same as when Pr. 340 = "0"
*1 Operation mode cannot be directly changed between the PU operation mode and Network operation mode.
*2 Operation mode can be changed between the PU operation mode and Network operation mode with of the operation panel and
X65 signal.
*3 Pr. 79 = "6" and Pr. 128 to Pr. 134 (PID control) are not activated simultaneously. Switchover mode and PID control are made invalid, and
the inverter performs the same operation as when "0" is set in Pr. 79.