70
PPO TYPE NON-SUPPORT SPECIFICATION
(2) PZD
Name Bit Definition
ZSW
Inverter running
(RUN signal)
0
0 : OFF
1 : ON (inverter running)
For master-to-slave messages (command
request), bits 0 to 7 are not used and must
be set to 0. The bit-wise data here do not
reflect Pr.190 to Pr.192 (output terminal
function selection).
At command response, signals are the
same. Signals are not affected by settings
of Pr.190 to Pr.192 (output terminal function
selection).
Forward running 1
0 : Other than forward running
(during stop or reverse rotation)
1 : Forward running
Reverse running 2
0 : Other than reverse running
(during stop or forward rotation)
1 : Reverse running
Up to frequency
(SU signal)
3
0 : OFF
1 : ON (up to frequency)
Overload alarm
(OL signal)
4
0 : OFF
1 : ON (overload alarm)
5 Not used (0 is returned)
Output frequency
detection
(FU signal)
6
0 : OFF
1 : ON (output frequency being
detected)
Fault output
(ALM signal)
7
0 : Inverter normal
1 : Inverter alarm occurrence
8 to 15 Not used (0 is returned)
HIW 0 to 15 Not used (0 is set)