Mitsumi electronic fr-a7np e Marine Battery User Manual


 
39
PROFIBUS DEVICE DATA
6
MaxTsdr_12M
200
Longest time 200 bit times at communication speed
12.0Mbps
Redundancy
0 Redundancy not supported.
Repeater_Ctrl_Sig
2 Installed as TTL level via RTS signal from module.
24V_Pins
0
24V power supply for maintenance device connection is not
used.
Freeze_Mode_supp
1 Freeze mode supported.
Sync_Mode_supp
1 Synchronous mode supported.
Auto_Baud_supp
1 Automatic baud rate detection support
Set_Slave_Add_supp
0 Slave address is not set.
Min_Slave_Intervall
1 100 μs interval between 2 polling cycles
Modular_Station
1 Modular device specified.
Max_Module
1 Maximum number of modules:1
Max_Input_Len
28 Input data: Maximum 28 bytes
Max_output_Len
28 Output data: Maximum 28 bytes
Max_Data_Len
56 Input and output data: Maximum 28 + 28 = 56 bytes
Fail_Safe
0 Failsafe not supported
Max_Diag_Data_Len
6 Diagnostic data of 6 bytes secured (no external diagnosis)
Slave_Family
1 Drives defined as function class (Main Family)
PrmText
1 Text selection 1 registration
Text(0)
"No byte swapping" If Bit 0 = 0, "No byte swapping"
Text(1)
"Byte swapping" If Bit 0 = 1, "Byte swapping"
EndPrmText
Parameter Value Description *1