Mitsumi electronic fr-a7np e Marine Battery User Manual


 
23
INVERTER SETTING
4
4.3 Start and speed command sources (Pr. 338, Pr. 339, Pr. 550)
(1) Select command source for the Network operation mode (Pr. 550)
A control location for the Network operation mode can be selected from either the RS-485
communication with the PU connector or a communication option.
When using a communication option, set "0 or 9999 (initial value)" in Pr. 550.
Refer to the inverter manual for details.
Parameter
Number
Name Initial Value
Setting
Range
Description
550
NET mode operation
command source selection
9999
0
The communication option is the
command source when NET
operation mode.
2
PU connector is the command source
when NET operation mode.
9999
Automatic communication option
recognition
Normally, PU connector is the
command source. When a
communication option is mounted,
the communication option is the
command source.