Mitsubishi Electronics FR-A700 Marine Battery User Manual


 
165
Frequency setting by external terminals
4
PARAMETERS
4.11 Frequency setting by external terminals
4.11.1 Multi-speed setting operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
(1) Multi-speed setting for 3 speeds (Pr. 4 to Pr. 6)
Operation is performed at the frequency set in Pr. 4 when the RH signal turns ON, Pr. 5 when the RM signal turns
ON, and Pr. 6 when the RL signal turns ON.
Purpose Parameter that must be Set Refer to Page
Make frequency setting by
combination of terminals
Multi-speed operation
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
165
Perform jog operation Jog operation Pr. 15, Pr. 16 167
Added compensation for multi-speed
setting and remote setting
Multi-speed input
compensation selection
Pr. 28 169
Infinitely variable speed setting by
terminals
Remote setting function Pr. 59 169
Can be used to change the preset speed in the parameter with the contact terminals.
Any speed can be selected by simply turning ON-OFF the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Name Initial Value Setting Range Description
4
Multi-speed setting (high
speed)
60Hz 0 to 400Hz Set the frequency when RH turns ON.
5
Multi-speed setting (middle
speed)
30Hz 0 to 400Hz Set the frequency when RM turns ON.
6
Multi-speed setting (low
speed)
10Hz 0 to 400Hz Set the frequency when RL turns ON.
24 Multi-speed setting (speed 4) 9999 0 to 400Hz, 9999
Frequency from speed 4 to speed 15
can be set according to the
combination of the RH, RM, RL and
REX signals.
9999: not selected
25 Multi-speed setting (speed 5) 9999 0 to 400Hz, 9999
26 Multi-speed setting (speed 6) 9999 0 to 400Hz, 9999
27 Multi-speed setting (speed 7) 9999 0 to 400Hz, 9999
232 Multi-speed setting (speed 8) 9999 0 to 400Hz, 9999
233 Multi-speed setting (speed 9) 9999 0 to 400Hz, 9999
234 Multi-speed setting (speed 10) 9999 0 to 400Hz, 9999
235 Multi-speed setting (speed 11) 9999 0 to 400Hz, 9999
236 Multi-speed setting (speed 12) 9999 0 to 400Hz, 9999
237 Multi-speed setting (speed 13) 9999 0 to 400Hz, 9999
238 Multi-speed setting (speed 14) 9999 0 to 400Hz, 9999
239 Multi-speed setting (speed 15) 9999 0 to 400Hz, 9999
REMARKS
In the initial setting, if two or three speeds are simultaneously selected, priority is given to the set frequency of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting.
By setting "0 (RL)", "1 (RM)", "2 (RH)" in any of Pr.178 to Pr.189 (input terminal function assignment), the signals can be assigned
to other terminals.
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
RH
Time
RM
RL
10
2
5
STF
RH
RM
RL
SD
Inverter
Multi-speed
selection
Frequency setting
potentiometer
Forward
rotation
Multi-Speed Operation
Connection Example