1.4 Applied motor (Pr. 71)
(1) Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is necessary when using a constant-torque motor. Thermal characteristic of the electronic
thermal relay function suitable for the motor is set.
When PM sensorless vector control is selected, the motor constants (MM-CF etc.) necessary for control
are selected as well.
Parameter
Number
Name
Initial
Value
Setting Range Description
71 Applied motor
0
0 to 8, 13 to 18, 20, 23,
24, 30, 33, 34, 40, 43,
44, 50, 53, 54, 330, 333,
334, 8093, 8094
Selecting the standard motor or constant-
torque motor sets the corresponding
motor thermal characteristic.
Pr. 71 Setting Motor
Electronic thermal relay
function operation
characteristic
Constant
torque
IPM
330* IPM Motor MM-CF
333
* IPM Motor MM-CF
Select "offline auto tuning setting"
8093 IPM Motor (other than MM-CF)
334
* IPM Motor MM-CF
Auto tuning data can be read,
changed, and set
8094 IPM Motor (other than MM-CF)
* The setting is available for FR-A720-11K or lower.
REMARKS
When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53, 333, 8093" in Pr. 71.
(Refer to page 7 for offline auto tuning)
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically
changed according to the Pr. 71 setting as follows.
Pr.71
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44,
330, 333, 334, 8093, 8094
Constant Torque
Motor Setting
1, 13 to 18, 50, 53, 54
Pr. 0 3% 2%