327
Selection of operation mode and operation location
4
PARAMETERS
[Explanation of table]
External : Control is valid only from external terminal signal.
NET : Control only from communication is valid
Combined : Control is valid from either of external terminal and communication.
: Control is invalid from either of external terminal and communication.
Compensation: Control by signal from external terminal is only valid when Pr. 28 Multi-speed input compensation selection = "1"
(6) Switching of command source by external terminal (X67)
In Network operation mode, the command source switching signal (X67) can be used to switch the start command
source and speed command source. This signal can be utilized to control the signal input from both the control
terminal and communication.
Set "67" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the X67 signal to the control terminal.
When the X67 signal is off, the start command source and speed command source are control terminal.
Selective function
Pr. 178 to Pr. 189 setting
42 X42
Torque bias selection 1
NET External
43 X43
Torque bias selection 2
NET External
44 X44
P/PI control switchover
NET External
60 STF
Forward rotation command
NET External
61 STR
Reverse rotation command
NET External
62 RES
Reset
External
63 PTC
PID forward action switchover
External
64 X64
PID forward action switchover
NET External NET External
65 X65
PU-NET operation switchover
External
66 X66
External-NET operation
switchover
External
67 X67
Command source switchover
External
68 NP
Simple position pulse train
sign
External
69 CLR
Simple position droop pulse
clear
External
70 X70
DC feeding operation
permission
NET External
71 X71
DC feeding cancel
NET External
74 X74
Magnetic flux decay output
shutoff
NET External
76 X76
Proximity dog
External
83 X83
0V calibration request
NET External
REMARKS
The command source of communication is as set in Pr. 550 and Pr. 551.
The Pr. 338 and Pr. 339 settings can be changed while the inverter is running when Pr. 77 = 2. Note that the setting change is
reflected after the inverter has stopped. Until the inverter has stopped, communication operation command source and
communication speed command source before the setting change are valid.
X67 Signal State Start Command Source Speed Command Source
No signal assignment
According to Pr. 338 According to Pr. 339
ON
OFF Command is valid only from control terminal signal.
REMARKS
The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched
during operation.
When the X67 signal is OFF, a reset via communication is disabled.
CAUTION
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
Parameters referred to
Pr. 28 Multi-speed input compensation selection Refer to page 169.
Pr. 59 Remote function selection Refer to page 169.
Pr. 79 Operation mode selection Refer to page 313.
Operation
Location
Selection
Pr. 338 Communication operation command
source
0: NET 1: External
Remarks
Pr. 339 Communication speed command
source
0: NET
1:External 2:External
0: NET
1:External 2:External