Frequency/torque setting by analog
input (terminal 1, 2, 4)
4
PARAMETERS
4.21 Frequency/torque setting by analog input (terminal 1, 2, 4)
4.21.1 Function assignment of analog input terminal (Pr. 858, Pr. 868)
For the terminal 1 and terminal 4 used for analog input, frequency (speed) command, magnetic flux command,
torque command, etc. can be selected.
Functions change according to the control mode as in the table below.
Terminal 1 function according to control
Terminal 4 function according to control
:No function
* This setting is valid under vector control.
Purpose Parameter that must be Set Refer to Page
Function assignment of analog input
terminal
Terminal 1 and terminal 4 function
assignment
Pr. 858, Pr. 868 285
Selection of voltage/current input
(terminal 1, 2, 4) Perform forward/
reverse rotation by analog input
Analog input selection Pr. 73, Pr. 267 286
Adjust the main speed by analog
auxiliary input
Analog auxiliary input and
compensation (added
compensation and override
function)
Pr. 73, Pr. 242, Pr. 243,
Pr. 252, Pr. 253
290
Noise elimination at the analog input Input filter
Pr. 74, Pr. 822, Pr. 826,
Pr. 832, Pr. 836, Pr. 849
292
Adjustment (calibration) of analog
input frequency and voltage (current)
Bias and gain of frequency
setting voltage (current)
Pr. 125, Pr. 126, Pr. 241,
C2 to C7 (Pr. 902 to Pr. 905)
C12 to C15 (Pr. 917 to Pr. 918)
294
Adjustment (calibration) of analog
input torque and voltage (current)
Bias and gain of torque setting
voltage (current)
Pr. 241,
C16 to C19 (Pr. 919 to Pr. 920),
C38 to C41 (Pr. 932 to Pr. 933)
300
Function assignment of terminal 1 and terminal 4 of analog input can be selected and changed by parameter.
Parameter
Number
Name Initial Value Setting Range Description
858 Terminal 4 function assignment
0 0, 1, 4, 9999
Select the terminal 4 function.
(Refer to the following list)
868 Terminal 1 function assignment
0 0 to 6, 9999
Select the terminal 1 function.
(Refer to the following list)
Pr. 868
Setting
V/F Control,
Advanced Magnetic
Flux Vector Control
Real Sensorless Vector Control, Vector Control Vector Control
Speed control Torque control Position control
0
(Initial value)
Frequency setting auxiliary Speed setting auxiliary Speed limit auxiliary
1 Magnetic flux command * Magnetic flux command * Magnetic flux command
2
Regenerative torque limit
(Pr. 810 = 1)
Regenerative torque
limit (Pr. 810 = 1)
3 ⎯⎯
Torque command
(Pr. 804 = 0)
4
Stall prevention operation
level input
(Pr. 810 = 1)
Torque limit (Pr. 810 = 1)
Torque command
(Pr. 804 = 0)
Torque limit (Pr. 810 = 1)
5 ⎯⎯
Forward/reverse rotation
speed limit (Pr. 807 = 2)
6
Torque bias input
(Pr. 840 = 1, 2, 3) *
⎯⎯
9999 ⎯⎯⎯
Pr. 858
Setting
V/F Control,
Advanced Magnetic Flux
Vector Control
Real Sensorless Vector Control, Vector Control Vector Control
Speed control Torque control Position control
0
(Initial value)
Frequency command
(AU signal-ON)
Speed command
(AU signal-ON)
Speed limit
(AU signal-ON)
1 Magnetic flux command * Magnetic flux command * Magnetic flux command
4
Stall prevention operation
level input
(Pr. 810 = 1)
Torque limit (Pr. 810 = 1) Torque limit (Pr. 810 = 1)
9999 ⎯⎯⎯