Mitsubishi Electronics FR-A700 Marine Battery User Manual


 
188
Selection and protection of a motor
(2) Use two types motors (Pr. 450)
Set Pr. 450 Second applied motor to use two types motors with one inverter.
When "9999" (initial value) is set, no function is selected.
When Pr. 450
9999, turning the RT signal ON makes the following parameter valid.
REMARKS
When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53" in Pr. 71.
(Refer to page 189 for offline auto tuning)
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
REMARKS
The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 235)
The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
CAUTION
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Parameters referred to
Pr. 0 Torque boost Refer to page 146
Pr. 12 DC injection brake operation voltage Refer to page 203
Pr. 80 Motor capacity, Pr. 81 Number of motor poles, Pr. 453 Second motor capacity, Pr. 454 Number of second motor poles Refer to page 148
Pr. 82 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 455 to Pr. 463, Pr. 859, Pr. 860 (Motor constant) Refer to page 189
Pr. 95 Online auto tuning selection, Pr. 574 Second motor online auto tuning Refer to page 199
Pr. 451 Second motor control method selection, Pr. 800 Control method selection Refer to page 92
Pr. 100 to Pr. 109 (Adjustable 5 points V/F) Refer to page 164
Pr. 71
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Constant Torque Motor Setting
1, 13 to 18, 50, 53, 54
Pr. 0 3% 2%
Pr. 12 4% 2%
Function
RT signal ON
(second
motor)
RT signal
OFF (first
motor)
Applied motor Pr. 450 Pr. 71
Control method selection Pr. 451 Pr. 800
Motor capacity Pr. 453 Pr. 80
Number of motor poles Pr. 454 Pr. 81
Motor excitation current Pr. 455 Pr. 82
Rated motor voltage Pr. 456 Pr. 83
Rated motor frequency Pr. 457 Pr. 84
Motor constant (R1) Pr. 458 Pr. 90
Motor constant (R2) Pr. 459 Pr. 91
Motor constant (L1) Pr. 460 Pr. 92
Motor constant (L2) Pr. 461 Pr. 93
Motor constant (X) Pr. 462 Pr. 94
Auto tuning setting/status Pr. 463 Pr. 96
Online auto tuning selection Pr. 574 Pr. 95
Torque current Pr. 860 Pr. 859
Function
RT signal ON
(second
motor)
RT signal
OFF (first
motor)