Monitor display and monitor output signal
4
PARAMETERS
(3) How to calibrate the terminal FM when using the operation panel (FR-DU07)
REMARKS
⋅ Calibration can also be made for external operation. Set the frequency in External operation mode, and make calibration in the
above procedure.
⋅ Calibration can be made even during operation.
⋅ For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
♦ Parameters referred to ♦
Pr. 54 FM terminal function selection Refer to page 253
Pr. 55 Frequency monitoring reference Refer to page 259
Pr. 56 Current monitoring reference Refer to page 259
Pr. 158 AM terminal function selection Refer to page 253
Pr. 291 Pulse train I/O selection Refer to page 378
Press to return to the display (step 4).
9.
Press . Setting is complete.
2.
Press to choose the parameter
setting mode.
3.
Turn until appears.
Flicker...Parameter setting complete!!
1.
Confirmation of the RUN indicator and
operation mode indicator
4.
Press to display .
6.
Press to enable setting.
7.
If the inverter is at a stop, (press
or ) to start the inverter.
(Motor needs not be connected.)
8.
Turn to adjust the indicator needle
to the desired position.
By turning , you can read another parameter.
(When Pr. 54=1)
Press twice to show the next parameter ( ).
Display
Operation
( )
The parameter
number read
previously appears.
C0 to C41
setting
is enabled.
Analog indicator
5.
Turn until appears.
Set to C0 FM terminal calibration.
The monitor set to Pr. 54 FM terminal
function selection is displayed.