Mitsubishi Electronics FR-A700 Marine Battery User Manual


 
278
Energy saving operation and energy saving monitor
4.19 Energy saving operation and energy saving monitor
4.19.1 Energy saving control (Pr. 60)
Energy saving operation mode (setting "4")
When "4" is set in Pr. 60, the inverter operates in the energy saving operation mode.
In the energy saving operation mode, the inverter automatically controls the output voltage to minimize the inverter
output voltage during a constant operation.
Purpose Parameter that must be Set
Refer to
Page
Energy saving operation Energy saving operation Pr. 60 278
How much energy can be saved Energy saving monitor
Pr. 52, Pr. 54, Pr. 158,
Pr. 891 to Pr. 899
279
Without a fine parameter setting, the inverter automatically performs energy saving control.
This inverter is optimum for fan and pump applications.
Parameter
Number
Name Initial Value Setting Range Description
60 Energy saving control selection* 0
0 Normal operation mode
4 Energy saving operation mode
* When parameter is read using the FR-PU04, a parameter name different from an actual parameter is displayed.
REMARKS
For applications a large load torque is applied to or machines repeat frequent acceleration/deceleration, an energy saving effect
is not expected.
CAUTION
When the energy saving mode is selected, deceleration time may be longer than the setting value. Since overvoltage alarm
tends to occur as compared to the constant torque load characteristics, set a longer deceleration time.
The energy saving operation mode functions only under V/F control. When the Advanced magnetic flux vector control, Real
sensorless vector control and vector control are selected, the energy saving mode is invalid.
Since output voltage is controlled in energy saving operation mode, output current may slightly increase.
V/F
V/F
V/F