4.6 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Input
˜
NOTE:
These values do not
affect the low or the
high set point limit
for process alarms.
[`rL1]
[`rH1]
Range Low 1 and
Range High 1
continued from
previous page.
[``°F] [``°C]
[`rL1] [`rH1] [`rL1] [`rH1]
[```r] [``32][3200] [```0][1760] 98_ _-2_ _-_ _ _
only
[`in1]
[```S] [``32][3200] [```0][1760]
[```b] [``32][3300] [```0][1816]
[`rtd] [-328][1472] [-200][`800]
[`r†d] [-9(9][99(9] [-7#3][53&7]
[4-20] [-999][9999] units
[0-20] [-999][9999] units
[`0-5] [-999][9999] units
[`1-5] [-999][9999] units
[0-10] [-999][9999] units
Calibration Offset 1
Offset the input 1 signal by a positive or negative value. This allows you
to compensate for lead resistance, sensor errors or other factors.
[CAL1] This prompt always appears.
If Default
[``°F] [-999] [```0] [9999]
[`C_F] [CAL1] [CAL1] [CAL1]
(Global Menu)
[``°F]
&
[`r†d] [-9(9] [``)0] [`9(9]
[`C_F] [`In1] [CAL1] [CAL1] [CAL1]
(Global Menu) (Input Menu)
[``°C] [-999] [```0] [9999]
[`C_F] [CAL1] [CAL1] [CAL1]
(Global Menu)
[``°C]
&
[`r†d] [-5%5] [``)0] [`5%5]
[`C_F] [`In1] [CAL1] [CAL1] [CAL1]
(Global Menu) (Input Menu)
[-999] [```0] [`999]
units
a process input
[CAL1] [CAL1] [CAL1]
is selected
[CAL1]