Watlow Electric 989 Marine Instruments User Manual


 
WATLOW Series 988 User’s Manual 4.7
Setup Menus, Chapter 4
Setup-Input
RTD (100) Calibration Curve 1
Select the calibration curve for the RTD 1 input. The RTD input uses
either the European (DIN, 0.003850//°C) or the Japanese (JIS,
0.003916//°C) linearization standard.
[rtd1] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].
Default
[`din] [`JIS]
[rtd1] [rtd1]
Software Filter 1
Select the filter time constant, in seconds, for input 1. This smooths a
rapidly changing input signal for display or control purposes.
• Select a positive value to filter only the display.
• Select a negative value to filter the input signal.
• Set the value to [```0] to disable the filter.
[Ftr1] This prompt always appears.
Default
[`-60] [```0] [``60]
[Ftr1] [Ftr1] [Ftr1]
[rtd1]
[Ftr1]