4.32 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Process 3
Select the range for the retransmit signal at output 3.
[Prc3] This prompt appears only on controllers equipped with retransmit
hardware (98_ _-_ _ _ _-M_ _ _ or 98_ _-_ _ _ _-N_ _ _) and with [Aout] not
set to [``no].
Default
4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[Prc3] [Prc3] [Prc3] [Prc3] [Prc3]
Retransmit Low Limit
Select the low limit for the retransmit signal at output 3.
• The default value is equal to [`rL1] or [`rL2] (in the Input Menu)
depending on whether [Aout] is set to [Prc1] or [Prc2].
• The decimal precision of [A`rL] is determined by [dEC1] (Input Menu) if
[Aout] is set to [Prc1] or [StPt]; it is determined by [dEC2] if [Aout] is
set to [Prc2].
[A`rL] This prompt appears only on controllers equipped with retransmit
hardware (98_ _-_ _ _ _-M_ _ _ or 98_ _-_ _ _ _-N_ _ _) and with [Aout] not
set to [``no].
[-999] [A`rH]
[A`rL] [A`rL]
˜
NOTE:
See Chapter 8 for
more information
on retransmit.
[A`rL]
[Prc3]