Watlow Electric 989 Marine Instruments User Manual


 
WATLOW Series 988 User’s Manual 4.19
Setup Menus, Chapter 4
Setup-Output
Output Prompts
When you are in the Setup menus, the Series 988 displays the menu
selection ( [InPt], [OtPt], [GLbL] or [COM] ) in the upper display, and
[`SEt] in the lower display.
The Up-arrow > or Down-arrow key < selects another menu. Press the
Mode key µ to display the first prompt in the lower display and its value
in the upper display. Use the Up-arrow > and Down-arrow < keys to
change the value in the upper display. The new value will not take effect
until after a five-second delay or until you press the Mode key µ.
Output 1
Set the way that output 1 will respond to a difference between the set
point and an input variable.
[``Ht] select reverse action, so that output 1 responds when the input
signal is less than the setpoint.
[``CL] select direct action, so that output 1 responds when the input
signal is more than the setpoint.
[`Ot1] This prompt always appears.
Default
[``Ht] [``CL]
[`Ot1] [`Ot1]
˜
NOTE:
Decimal points may
not always be in the
position specified
below depending
on the the settings
in the Decimal 1
[deC1] and Decimal
2 [deC2] parame-
ters in the Input
Menu.
[`Ot1]