Watlow Electric 989 Marine Instruments User Manual


 
4.20 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Process 1
Select the process range for output 1.
[Prc1] This prompt appears only on controllers equipped with output 1
process hardware (98_ _-_ _F_-_ _ _ _).
Default
4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[Prc1] [Prc1] [Prc1] [Prc1] [Prc1]
Hysteresis 1
Select the switching hysteresis for output 1. This determines the
change in temperature or process units needed to turn the output from
full on to full off.
[HYS1] This prompt does not appear on controllers equipped with output 1
process hardware (98_ _-_ _F_-_ _ _ _). This prompt only appears with the
controller set up as an on/off controller ( [PBIA] = [```0] ).
If Default
[``°F] [```1] [```3] [`999]
[`C_F] [HYS1 ][HYS1] [HYS1]
(Global Menu)
[``°F]
&
[`r†d] [``)1] [``#0] [`9(9]
[`C_F] [`In1] [HYS1] [HYS1] [HYS1]
(Global Menu) (Input Menu)
[``°C] [```1] [```2] [`555]
[`C_F] [HYS1] [HYS1] [HYS1]
(Global Menu)
[``°C]
&
[`r†d] [``)1] [``@0] [`5%5]
[`C_F] [`In1] [HYS1] [HYS1] [HYS1]
(Global Menu) (Input Menu)
[```1] [```3] [`999]
units
a
process input
[HYS1] [HYS1] [HYS1]
is selected
[HYS1]
[Prc1]