AEG PV.630 Marine Battery User Manual


 
Protect PV.630 Operating Instructions
42 of 72 8000047961 BAL
6.2 Table of Faults
The monitoring systems listed below will cause the inverter to switch off, are self-
acknowledging or signalling and are shown on the DOU with corresponding plain text:
Temperature monitoring systems
Fault/Message
Deac-
tivat-ing
Self-
acknow-led
ging
Signalling
DOU message
IGBT 1 stack temperature warning X !Equipment temperature fault!
IGBT 2 stack temperature warning X !Equipment temperature fault!
IGBT 1 stack temperature fault X #Equipment temperature fault#
IGBT 2 stack temperature fault X #Equipment temperature fault#
IGBT supply air undertemperature X !Ambient temperature fault!
IGBT supply air temperature
warning
X !Ambient temperature fault!
IGBT supply air temperature fault X #Ambient temperature fault#
Unit exhaust air 1
temperature warning
X !Equipment temperature fault!
Unit exhaust air 2
temperature warning
X !Equipment temperature fault!
Unit exhaust air 1
temperature fault
X #Equipment temperature fault#
Unit exhaust air 2
temperature fault
X #Equipment temperature fault#
Equipment supply air under-
temperature
X !Ambient temperature fault!
Unit supply air temperature warn-
ing
X !Ambient temperature fault!
Unit supply air temperature fault X #Ambient temperature fault#
Temperature sensor fault
IGBT 1 stack
X #Temperature sensor fault#
Temperature sensor fault
IGBT 2 stack
X #Temperature sensor fault#
Temperature sensor fault
IGBT supply air temperature
X #Temperature sensor fault#
Temperature sensor fault
unit exhaust air 1 temperature
X #Temperature sensor fault#
Temperature sensor fault
unit exhaust air 2 temperature
X #Temperature sensor fault#
Temperature sensor fault unit
supply air temperature
X #Temperature sensor fault#
IGBT difference current deviation X !Difference current deviation!