AEG PV.630 Marine Battery User Manual


 
Protect PV.630 Installation and Start-up
80000047963 BAL 5 of 21
4 Transport, Storage and Installation
4.1 Packaging
The system or the individual control cabinets are fastened to
transport pallets and packed at the factory to withstand both rail
and road transport. The system or the individual control cabinets
are packed in plastic film to prevent any damage to the surface
paint and to protect against moisture.
4.2 Storage
Only store the system or the individual control cabinets for a max-
imum period of six months in the original packaging in dry, venti-
lated rooms with a permanent roof. The permissible ambient tem-
perature range is between -35°C and +70°C with a relative humidi-
ty of 85%.
If the system or the individual control cabinets are stored for longer
than six months, they must first be packed with standard desic-
cants and then sealed in airtight plastic film.
i
To prevent damage, only remove the protective film from
the system or the individual control cabinets immediately
prior to installation.
4.3 Installation Site Requirements, Operating Area
The system is intended for installation in areas which are difficult to
access.
The system is intended for operation in a station (container) by de-
fault. The system must be installed in such a way that the supply
air and exhaust air ducts can ensure sufficient cooling of the INV
control cabinet. Access must facilitate replacement of the fans and
opening of the cleaning flap.
If the system is not operated in a wall-mounted station, additional
measures must be taken to ensure that there is sufficient cooling
of the INV control cabinet in particular and that the exhaust air
cannot get back in through the supply air openings.
Suitable floor surfaces for installation of the system are:
Double floors
Above cable ducts or
Directly on a level surface
Ensure that the weight of the system does not exceed the max-
imum floor bearing capacity.
Observe the applicable fire protection requirements.