Install and Cable the Cabinets
Page 1-86Install Off-Premises Station Wiring
1
Figure 1-40 shows the connections for up to 24 off-premises analog telephones.
Concentrations of analog line pairs are used at both buildings to minimize the
off-premises wiring required. At the MDF, jumpers must be connected between 1
row/connecting block in the white field and up to 3 rows/connecting blocks in the
purple field. At the station location, a WP-90929, List 1 Concentrator Cable is
used. There are 8 station appearances on each of the 3 fingers of the
concentrator cable.
Figure 1-40. Connections to 24 Out-of-Building Telephones
Figure Notes
1. Locally engineered cables
2. Multi-pair protector units (primary
protectors with heat coils or equivalent with
sneak current protection)
3. B25A cable
4. Concentrator cable (WP90929 List 1)
5. 356A adapter
6. Out-of-building wiring
7. Out-of-building analog telephones
8. Part of MDF
9. Station side (white field)
10. System side (purple field)
11. Cross-connect jumpers
12. To TN2183, TN769, TN742, or
TN746B analog line circuit pack
crdf24o RPY 012398