6. TROUBLESHOOTING
6 - 1
6. TROUBLESHOOTING
POINT
Alarms and warnings are basically the same as those of MR-J3- B servo
amplifier. This chapter describes the contents different from those of MR-J3-
B
servo amplifier.
As soon as an alarm occurs, make the servo-off status and interrupt the main
circuit power.
If an alarm has occurred, refer to this chapter and remove its cause.
6.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. Refer to section 6.2 of
this manual and section 8.2 of the MR-J3-
B Servo Amplifier Instruction Manual at an alarm occurrence and
section 6.3 of this manual and section 8.3 of the MR-J3-
B Servo Amplifier Instruction Manual at a warning
occurrence, and then take the appropriate action. When an alarm occurs, the ALM turns off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked
in the alarm
deactivation column. The alarm is automatically canceled after removing the cause of occurrence.
Alarm deactivation Display Name
92 Battery cable disconnection warning
Display Name
Power
off
on
Error
reset
CPU
reset
96 Home position setting error
10 Undervoltage 9F Battery warning
12 Memory error 1 (RAM) E0 Excessive regeneration warning
13 Clock error E1 Overload warning 1
15 Memory error 2 (EEP-ROM) E2 Direct drive motor overheat warning
16 Encoder error 1 E3 Absolute position counter warning
17 Board error E4 Parameter warning
19 Memory error 3 (Flash-ROM) E6 Servo forced stop warning
1A Motor combination error E7 Controller forced stop warning
1F Encoder combination error Cooling fan speed reduction
20 Encoder error 2
E8
warning
21 Encoder error 3 E9 Main circuit off warning
24 Main circuit error EC Overload warning 2
25 Absolute position erase
Warnings
ED Output watt excess warning
27 Initial magnetic pole detection error
2B Encoder counter error
30 Regenerative error (Note 1) (Note 1) (Note 1)
31 Overspeed
32 Overcurrent
33 Overvoltage
34 Receive error 1 (Note 2)
35 Command frequency alarm
36 Receive error 2
37 Parameter error
42 Servo control error (Note 3) (Note 3)
45 Main circuit device overheat (Note 1) (Note 1) (Note 1)
46 Direct drive motor overheat (Note 1) (Note 1) (Note 1)
47 Cooling fan alarm
50 Overload 1 (Note 1) (Note 1) (Note 1)
51 Overload 2 (Note 1) (Note 1) (Note 1)
52 Error excessive
8A USB communication time-out error
8E USB communication error
Alarms
888 Watchdog
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. In some controller communication status, the alarm factor may not be removed.
3. Set parameter No.PS04 to "1
" to deactivate.