43
Calibration of the Meter (Frequency Meter)
2
2.5.2 Calibration of the AM terminal
This section provides a way to calibrate the meter
connected to terminal AM using the parameter unit.
(1) Calibration procedure 1
(Example: To calibrate the meter at the
running frequency of 60Hz)
7
Press .
Calibration is complete.
8
Press to return to the
main monitor screen.
REMARKS
When FR-PU07BB is used in the battery mode (the
inverter power is OFF), this parameter cannot be set
(calibrated).
Completed
<MONITOR>
900 FM Tune
60.00Hz
STF FWD PU
READ
:
List
Parameter
Pr. 901 AM terminal calibration
Pr. 158 AM terminal function selection
Pr. 55 Frequency monitoring reference
Pr. 56 Current monitoring reference
1
Press .
The frequency setting screen
appears, and operation mode
changes to PU operation mode.
2
Press .
The parameter unit is in the
parameter setting mode.
3
Enter and
press
.
The preset frequency is
displayed.
Freq Set
SET 0.00Hz
0~400Hz
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
Run Inverter
0.00Hz
901 AM Tune
PU