Mitsumi electronic FR-PU07/FR-PU07BB Marine Battery User Manual


 
87
Combined Operation (Operation Using External Input Signals and PU)
4
4.3.2 Entering the running frequency from outside and making start and stop
from the PU (Pr. 79 = 4)
Step Operation Procedure Image
1
Switch the power ON.
2
Set "4" in Pr. 79 Operation
mode selection.
The External/PU combined
operation mode is selected
and the operation mode
indication on the display
changes to "PU + E".
3
Enter the external
frequency command. Select
the multi-speed signal or
turn the frequency setting
potentiometer.
ON
1. Power on
2.Operation mode selection
0.00Hz
---STOPPU+E
READ
:
List
3. Running frequency
ON
High speed
Low speed
Middle speed
or
4
Press or of the
parameter unit.
The motor starts running,
and the state of the output
frequency is shown on the
display.
·The starting terminals (STF,
STR) of the inverter are invalid.
·The inverter may also be
started by pressing the PU
or and then
inputting the frequency
command.
5
Press of the
parameter unit.
The motor is decelerated to
a stop.
REMARKS
·
When FR-PU07BB is used in the battery mode (the
inverter power is OFF), the operation is not available.
Step Operation Procedure Image
4. Start
(or)
60.00Hz
STFSTOPPU+E
READ
:
List
5. Stop
Stop