Mitsumi electronic FR-PU07/FR-PU07BB Marine Battery User Manual


 
44
Calibration of the Meter (Frequency Meter)
(2) When calibrating output current
For the output current or another item, which does
not easily point 100% value during operation,
adjust the reference voltage output, then select the
item to be displayed.
4
Enter and press
.
60Hz is set.
5
Press .
Forward rotation is performed
at 60Hz. You need not
connect the motor.
6
Using / , adjust the meter pointer to a
predetermined position.
The meter pointer moves. (It takes a long time before
the pointer moves.)
7
Press .
Calibration is complete.
8
Press to return to the
main monitor screen.
Run Inverter
60Hz
901 AM Tune
PU
MntrF 60.00Hz
901 AM Tune
<WRITE>PU
Completed
<MONITOR>
901 AM Tune
60.00Hz
STF FWD PU
READ
:
List
1
Press .
The frequency setting screen
appears, and operation mode
changes to PU operation mode.
2
Press .
The parameter unit is in the
parameter setting mode.
3
Enter and
press
.
The present Pr. 158 setting
appears.
4
Enter and press .
The setting of reference
voltage output is complete.
5
Press .
The parameter unit is in the
parameter setting mode.
Freq Set
SET 0.00Hz
0~400Hz
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
1
158 AM set
21
21
158 AM set
Completed
SETTING MODE
0~9:Ser Pr.NO.
Select Oper