Adjustment of the Frequency Setting Signals "Bias" and "Gain"
2.6 Adjustment of the Frequency Setting Signals "Bias" and "Gain"
The functions vary with the inverter model. (Refer to the inverter instruction manual for details of the
functions.)
2.6.1 Adjustment procedure
There are three ways to adjust the bias and gain of the frequency setting voltage (current).
(1) Adjust only the bias and gain frequencies and not adjust the voltage (current) (Refer to page 47)
(2) Adjust any point by applying a voltage across terminals 2-5 (starting a current across terminals 4-5)
(Refer to page 49)
(3) Adjust any point without a voltage being applied across terminals 2-5 (without a current being applied
across terminals 4-5) (Page 51)
REMARKS
When using FR-PU07BB in the battery mode, only Adjustment procedure (3) is available for the following calibration
parameters.
Parameter
Pr. 902 Terminal 2 frequency setting bias frequency
Pr. 903 Terminal 2 frequency setting gain
Pr. 904 Terminal 4 frequency setting bias frequency
Pr. 905 Terminal 4 frequency setting gain
FR-A700 FR-F700 FR-E700
Pr. 902 to Pr. 905, Pr. 917 to Pr.
920, Pr. 932, Pr. 933
Pr. 902 to Pr. 905 Pr. 902 to Pr. 905, Pr. 922, Pr. 923