76
Operation Procedures for Functions
3.2.12 Multiple copies
(1) Copying the parameter settings
Parameter settings of an inverter can be read. The settings of maximum three inverters can be stored in
the FR-PU07. You can also copy the stored parameter settings to another inverter of the same series.
Confirm for setting
· Is the PU operation mode selected? → If not, press to select the PU operation mode.
· Is the inverter stopped? → If it is running, press to stop it.
·Is the Pr. 77 setting of the copy destination inverter correct? → Set "0 or 2" in Pr. 77.
· Is the inverter of the copy destination the same series as that of the copy source?
→
Select the inverter of the same series.
Example:{ FR-A720-0.4K → FR-A720-0.75K Parameters can be copied only to the
× FR-A720-0.4K → FR-F720-0.75K same series inverters.
CAUTION
Turning power OFF during parameter copy (read, write) as below, processing is not completely ended.
Perform parameter copy again.
· Turn OFF the inverter power.
· The FR-PU07BB (battery mode) power is OFF or battery exhaustion.
· Remove the FR-PU07 from the inverter.
· Pull out the PU cable.