PowerLogic™ PM5300 series Chapter 15—MID Compliance
© 2014 Schneider Electric All Rights Reserved 111
Setting up the PM5331/PM5341
You must configure all the lock-protected setup parameters before locking the meter.
When the meter is locked, those setup parameters cannot be edited.
Basic setup menu
See “Configuring the basic setup parameters” on page 34 to perform basic setup.
For MID compliance, the Power System must be set to one of the following settings:
• 3PH4W Wye Gnd (three-phase 4-wire wye grounded)
• 3PH3W Wye Ungnd (three-phase 3-wire wye ungrounded)
Advanced setup menu
See “Advanced setup” on page 41 to perform advanced setup.
You must use ION Setup to edit the device label.
Clock setup menu
See “Setting the clock” on page 41 to change the meter time using the display.
You can also use ION Setup to set or sync the meter time.
Tariff setup menu
See “Multi-tariff feature overview” on page 83 to configure the energy tariffs.
Passwords setup menu
See “Setting up the screen passwords” on page 39 to change the meter screen
passwords.
Initializing the meter
Initializing the meter clears the meter’s logged data, counters and timers. It is common
practice to initialize the meter after its configuration is complete, before adding it to an
energy management system.
1. After configuring all the meter setup parameters, navigate through the different
meter display screens and make sure the displayed data is valid.
2. See “Meter resets” on page 99 for instructions on clearing the meter’s recorded
logged data, counters and timers.
3. Select Meter Initialization to clear all recorded data.
Lock-protected functions
Menu Sub-menu Lock-protected function
Resets
Global Resets
• Meter Initialization (all)
•Energies
Single Resets
•Energy
• Multi-Tariff