Chapter 6—Input / Output PowerLogic™ PM5300 series user guide
Related topics
See “Technical Specifications” on page 15 for electrical characteristics and limits for
the status inputs.
Status input setup
The status input ports (S1 and S2) can be configured using the front panel or
ION Setup software.
NOTE: It is recommended you use ION Setup to configure the status inputs, as setup
parameters that require text entry can only be modified using ION Setup.
Configuring status inputs using ION Setup
You can use ION Setup to configure the status inputs.
1. Start ION Setup.
2. Connect to your meter.
3. Navigate to I/O configuration > I/O Setup.
4. Select a status input to configure and click Edit. The setup screen for that status
input is displayed.
5. Enter a descriptive name for the status input’s Label.
6. Configure the other setup parameters as required.
7. Click Send to save your changes.
Status input setup parameters available through ION Setup
Parameter Values Description
Label
Use this field to change the default label and assign a
descriptive name to this status input.
Control Mode
Normal, Demand Sync, Input
Metering
This field displays how the status input functions.
Normal: the status input is not associated with
another meter function. The meter counts and
records the number of incoming pulses normally.
Demand Sync: the status input is associated with
one of the input sync demand functions. The meter
uses the incoming pulse to synchronize its demand
period with the external source.
Input Metering: the status input is associated with
one of the input metering channels. The meter
counts and records the number of incoming pulses
and related consumption data associated with the
pulses.
Debounce 0 to 9999
Debounce is the time delay that compensates for
mechanical contact bounce. Use this field to set how
long (in milliseconds) the external signal must remain in
a certain state to be considered a valid state change.
Associations
This field displays additional information if the status
input is already associated with another meter function.