Chapter 6—Input / Output PowerLogic™ PM5300 series user guide
Digital output applications
Digital outputs are typically used in switching applications, for example, to provide
on/off control signals for switching capacitor banks, generators, and other external
devices and equipment. They can also be used in demand synchronization
applications, where the meter provides pulse signals to the input of another meter to
control its demand period.
The digital output can also be used in energy pulsing applications, where a receiving
device determines energy usage by counting the kWh pulses coming from the meter’s
digital output port.
NOTE: Be aware that an unexpected change of state of the digital outputs may result
when the supply power to the meter is interrupted or after a meter firmware upgrade.
Digital output application example
You can connect your meter’s digital outputs to other meters to send a demand sync
pulse. In the following example, the first meter (Meter 1) controls and sets the demand
period of the other meters (Meter 2, Meter 3, Meter 4) through the output pulse
occurring at the end of the first meter’s demand interval.
Related topics
See “Technical Specifications” on page 15 for electrical characteristics and limits for
the digital outputs.
Digital output setup
The digital output ports (D1 and D2) can be configured using the front panel or
ION Setup.
NOTE: It is recommended you use ION Setup to configure the digital outputs, as setup
parameters that require text entry can only be modified using software.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E in the USA or applicable local standards.
Turn off all power supplying this device before working on it.
Always use a properly rated voltage sensing device to confirm that all power is off.
Do not exceed the device’s ratings for maximum limits.
Do not use this device for critical control or protection applications where human or
equipment safety relies on the operation of the control circuit.
Failure to follow these instructions will result in death or serious injury.
Digital output wiring example
S1 S2D1 D2 -/C +
(60) (62)
(40) (42) (57) (56)
S1 -/C S1 -/C S1 -/C
< 20mA
< 40Vdc < 40Vdc
< 20mA
Meter 2 Meter 3 Meter 4
Meter 1