PowerLogic™ PM5300 series user guide Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved70
Setting Up Digital Alarms
To set up digital alarms:
1. Press Dig. The digital alarm
Select screen appears.
2. Press and to scroll
through the list of digital
alarms.
3. Press Edit to select an alarm to
be configured.
4. Press Edit to select Pickup
Setpoint, then press Edit.
5. Press + and - to scroll between
On and Off.
6. Press OK to enter the pickup
setpoint.
7. Press to select Pickup Time
Delay, then press Edit.
NOTE: If the selected status
input mode is Demand Sync or
Input Metering, a confirmation
screen appears warning that if
an alarm is enabled for this
status input, the existing
association will be broken.
8. Press + to increment the active
digit through the numerals 0-9.
NOTE: Units for time delays
are set in seconds.
9. Press to enter the selected
value for the active digit and
move to the next digit to the
left.
10. Continue until all values are
selected, then press OK to
enter the pickup time delay.
11. Press
to select Dropout
Time Delay, then press Edit.
12. Follow Steps 8 to 11 for the
dropout time delay.