Schneider Electric PM5300 Marine Instruments User Manual


 
PowerLogic™ PM5300 series user guide Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved 29
Related topics
See “Digital output applications” on page 52 for digital output use and configuration
details.
Status inputs
The meter is equipped with two status input ports (S1 and S2). You can configure the
status inputs for use in status monitoring applications.
The meter’s status inputs require an external voltage source to detect the status input’s
on/off state. The meter detects an ON state if the external voltage appearing at the status
input is within its operating range.
The external voltage can be derived from either the whetting output provided by the meter
or by a voltage source up to 36 V DC external to the meter.
Relay outputs
The meter is equipped with two Form A mechanical relay output ports (Relay 1 and Relay
2). Relay outputs can be configured to be used switching applications, for example, to
provide on/off control signals for switching capacitor banks, generators, and other
external devices and equipment.
Digital output connections
S1 S2D1 D2 -/C +
(60) (62)
(40) (42) (57) (56)
LOAD
LOAD
< 20mA
< 20mA
< 40Vdc < 40Vdc
Status input connections
S1 S2D1 D2 -/C +
(60) (62)
(40) (42) (57) (56)