Schneider Electric PM5300 Marine Instruments User Manual


 
PowerLogic™ PM5300 series user guide Chapter 8—Data Logs
© 2014 Schneider Electric All Rights Reserved 75
Chapter 8—Data Logs
This chapter briefly describes the following logs of the power and energy meter:
Alarm Log
User-defined data log
Logs are files stored in the non-volatile memory of the power and energy meter and are
referred to as “on-board logs”.
Data Logs
The PM5300 series records and stores readings at regularly scheduled intervals in one
independent data log. This log will be in disabled state from the factory. You can set up
the data log to store the following information.
Time Interval: 15, 30, 60 minutes
First-in-first-out (FIFO) or Fill and Hold
Values logged - up to 2 registers along with data and time of each log entry
The registers list for configuring the data logs
Description Number of Registers Data Type Register Number
Active energy delivered 4 Integer 3204
Active energy received 4 Integer 3208
Reactive energy delivered 4 Integer 3220
Reactive energy received 4 Integer 3224
Apparent energy delivered 4 Integer 3236
Apparent energy received 4 Integer 3240
Status input 1 counter 1 Integer 8915
Status input 2 counter 1 Integer 8919