PowerLogic™ PM5300 series user guide Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved 69
Setting Up Unary Alarms
To set up unary alarms:
1. Press Unary. The unary alarm
Select screen appears.
2. Press and to scroll
through the list of unary alarms.
3. Press Edit to select an alarm to
be configured.
4. Press Edit to select Enable.
5. Press + and - to scroll between
Yes and No.
6. Press OK to enable or disable
the alarm.
7. Press
to select Priority.
8. Press + and - to scroll through
priority options Low, None,
High, or Medium.
NOTE: See “Alarm Priorities”
on page 66 for more
information.
9. Press OK to set the priority.
10. Press
to select Select
Digital Output, then press Edit.
NOTE: The digital output
behavior mode must be Timed
or Coil Hold to turn on when a
unary alarm event occurs.
11. Press + and - to scroll through
the list of digital outputs to
associate with the alarm.
12. Press OK to select a digital
output to be associated with the
selected alarm.
13. If the selected digital output
already has an association that
will be lost by making the new
selection, a confirmation
screen appears.
Press Yes to accept the
changes and return to the
previous screen.
Press No to keep the
existing configuration in use
and return to the previous
screen.
14. Press
to save all alarms
selections and return to the
previous screen.
15. Press
to save all unary
alarm selections.