Mitsubishi Electronics FR-F700 Marine Battery User Manual


 
23
66
Stall prevention operation reduction
starting frequency
0 to 400Hz 0.01Hz 60Hz 30
Retry
67
Number of retries at alarm occurrence 0 to 10, 101 to 110 1 0 34
68
Retry waiting time 0 to 10s 0.1s 1s 34
69
Retry count display erase 0 1 0 34
70
Special regenerative brake duty *2 0 to 10% 0.1% 0% 31
71
Applied motor 0, 1, 2, 20 1 0 34
72
PWM frequency selection 0 to 15/0 to 6, 25*1 1 2 35
73
Analog input selection 0 to 7, 10 to 17 1 1 35
74
Input filter time constant 0 to 8 1 1 36
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17 1 14 36
76
Alarm code output selection 0, 1, 2 1 0 36
77
Parameter write selection 0, 1, 2 1 0 36
78
Reverse rotation prevention selection 0, 1, 2 1 0 36
79
Operation mode selection 0, 1, 2, 3, 4, 6, 7 1 0 37
Simple
magnetic flux
vector control
80
Motor capacity (simple magnetic flux
vector control)
0.4 to 55kW, 9999
/0 to 3600kW, 9999
*1
0.01/0.1kW*1 9999 37
90
Motor constant (R1)
0 to 50, 9999
/0 to 400m, 9999
*1
0.001/
0.01m
*1
9999 37
Adjustable 5 points V/F
100
V/F1 (first frequency) 0 to 400Hz, 9999 0.01Hz 9999 38
101
V/F1 (first frequency voltage) 0 to 1000V 0.1V 0V 38
102
V/F2 (second frequency) 0 to 400Hz, 9999 0.01Hz 9999 38
103
V/F2 (second frequency voltage) 0 to 1000V 0.1V 0V 38
104
V/F3 (third frequency) 0 to 400Hz, 9999 0.01Hz 9999 38
105
V/F3 (third frequency voltage) 0 to 1000V 0.1V 0V 38
106
V/F4 (fourth frequency) 0 to 400Hz, 9999 0.01Hz 9999 38
107
V/F4 (fourth frequency voltage) 0 to 1000V 0.1V 0V 38
108
V/F5 (fifth frequency) 0 to 400Hz, 9999 0.01Hz 9999 38
109
V/F5 (fifth frequency voltage) 0 to 1000V 0.1V 0V 38
PU connector
communication
117
PU communication station 0 to 31 1 0 38
118
PU communication speed 48, 96, 192, 384 1 192 38
119
PU communication stop bit length. 0, 1, 10, 11 1 1 38
120
PU communication parity check 0, 1, 2 1 2 38
121
Number of PU communication retries 0 to 10, 9999 1 1 38
122
PU communication check time interval 0, 0.1 to 999.8s, 9999 0.1s 9999 38
123
PU communication waiting time setting 0 to 150ms, 9999 1 9999 38
124
PU communication CR/LF presence/
absence selection
0, 1, 2 1 1 38
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz 0.01Hz 60Hz 39
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz 0.01Hz 60Hz 39
PID operation
127
PID control automatic switchover
freqeuncy
0 to 400Hz, 9999 0.01Hz 9999 39
128
PID action selection
10, 11, 20, 21, 50, 51, 60,
61
1 10 39
129
PID proportional band 0.1 to 1000%, 9999 0.1% 100% 39
130
PID integral time 0.1 to 3600s, 9999 0.1s 1s 39
131
PID upper limit 0 to 100%, 9999 0.1% 9999 39
132
PID lower limit 0 to 100%, , 9999 0.1% 9999 39
133
PID action set point 0 to 100%, 9999 0.01% 9999 39
134
PID differential time 0.01 to 10.00s, 9999 0.01s 9999 39
*1 Differ according to capacities. (55K or less/75K or more)
*2 Setting can be made for the 75K or more.
Function
Parameters
Name Setting Range Increments Initial Value
Refer to
page