indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Pr.
The time constant of the primary delay filter relative to external
frequency command (analog input (terminal 1, 2, 4) signal) can
be set.
Valid for eliminating noise of the frequency setting circuit.
Increase the filter time constant if steady operation cannot be
performed due to noise.
A larger setting results in slower response. (The time constant can
be set between approximately 10ms to 1s with the setting of 0 to 8.)
You can select the reset input acceptance, disconnected PU
(FR-DU07) connector detection function and PU stop function.
Reset selection
You can select the operation timing of reset function (RES
signal, reset command through communication) input
Disconnected PU detection
This function detects that the PU (FR-DU07/FR-PU04) has
been disconnected from the inverter for longer than 1s and
causes the inverter to provide an alarm output (E.PUE) and
come to an alarm stop.
PU stop selection
In any of the PU operation, external operation and network
operation modes, the motor can be stopped by pressing
of
the PU.
At alarm occurrence, its description can be output as a 4-bit
digital signal from the open collector output terminals.
The alarm code can be read by a programmable controller, etc.,
and its corrective action can be shown on a display, etc.
The following table indicates alarm codes to be output. (0: output
transistor off, 1: output transistor on)
You can select whether write to various parameters can be
performed or not. Use this function to prevent parameter values
from being rewritten by misoperation.
This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.
Noise elimination at the analog
input
Pr.74 Input filter time constant
Reset selection, disconnected PU
detection
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Pr.75
Setting
Reset Selection
Disconnected
PU Detection
PU Stop
Selection
0
Reset input normally
enabled.
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the
motor to a stop only
in the PU operation
mode.
1
Reset input enabled
only when the protective
function is activated.
2
Reset input normally
enabled.
When the PU is
disconnected,
the inverter
output is shut
off.
3
Reset input enabled
only when the protective
function is activated.
14
(initial
value)
Reset input normally
enabled.
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the
motor to a stop in
any of the PU,
external and
communication
operation modes.
15
Reset input enabled
only when the protective
function is activated.
16
Reset input normally
enabled.
When the PU is
disconnected,
the inverter
output is shut
off.
17
Reset input enabled
only when the protective
function is activated.
Pr.
74
Pr.
75
Output function of alarm code
Pr.76 Alarm code output selection
Pr.76 Setting Description
0 (initial value) Without alarm code output
1 With alarm code output (Refer to the following table)
2
Alarm code output at alarm occurrence only (Refer to
the following table)
Operation Panel
Indication
(FR-DU07)
Output of Output Terminals
Alarm Code
SU IPF OL FU
Normal * 0 0 0 0 0
E.OC1 0 0 0 1 1
E.OC2 0 0 1 0 2
E.OC3 0 0 1 1 3
E.OV1 to E.OV3 0 1 0 0 4
E.THM 0 1 0 1 5
E.THT 0 1 1 0 6
E.IPF 0 1 1 1 7
E.UVT 1 0 0 0 8
E.FIN 1 0 0 1 9
E.BE 1 0 1 0 A
E. GF 1 0 1 1 B
E.OHT 1 1 0 0 C
E.OLT 1 1 0 1 D
E.OPT 1 1 1 0 E
E.OP1 1 1 1 0 E
Other than the
above
1 1 1 1 F
* When Pr. 76 = "2", the output terminals output the signals assigned to
Pr.
190 to Pr. 196.
Prevention of parameter rewrite
Pr.77 Parameter write selection
Pr. 77 Setting Description
0 (initial value) Write is enabled only during a stop
1 Parameter write is not enabled.
2
Parameter write is enabled in any operation
mode regardless of operation status.
Prevention of reverse rotation of
the motor
Pr.78 Reverse rotation prevention selection
Pr.78 Setting Description
0 (initial value) Both forward and reverse rotations allowed
1 Reverse rotation disabled
2 Forward rotation disallowed
Pr.
76
Pr.
77
Pr.
78