Mitsubishi Electronics FR-F700 Marine Battery User Manual


 
Features
Standard
Specifications
Outline
Dimension
Drawings
Operation
Panel
Protective
Functions
OptionsInstructionsMotorCompatibilityWarrantyInquiry
Peripheral Devices
Why energy
savings?
Terminal Connection
Diagram
Terminal Specification
Explanation
Parameter
List
Explanations
of
Parameters
24
Commercial power
supply-inverter
switch-over
135
Commercial power-supply switchover
sequence output terminal selection
0, 1 1 0 39
136
MC switchover interlock time 0 to 100s 0.1s 1s 39
137
Waiting time at a start 0 to 100s 0.1s 0.5s 39
138
Commercial power-supply operation
switchover selection at an alarm
0, 1 1 0 39
139
Automatic switchover frequency
between inverter and commercial power-
supply operation
0 to 60Hz, 9999 0.01Hz 9999 39
Backlash
measures
140
Backlash acceleration stopping
frequency
0 to 400Hz 0.01Hz 1Hz 30
141
Backlash acceleration stopping time 0 to 360s 0.1s 0.5s 30
142
Backlash deceleration stopping
frequency
0 to 400Hz 0.01Hz 1Hz 30
143
Backlash deceleration stopping time 0 to 360s 0.1s 0.5s 30
144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102, 104,
106, 108, 110
1 4 31
PU
145
PU display language selection 0 to 7 1 0 40
Current detection
148
Stall prevention level at 0V input. 0 to 150% 0.1% 120% 30
149
Stall prevention level at 10V input. 0 to 150% 0.1% 150% 30
150
Output current detection level 0 to 150% 0.1% 120% 40
151
Output current detection signal delay
time
0 to 10s 0.1s 0s 40
152
Zero current detection level 0 to 150% 0.1% 5% 40
153
Zero current detection time 0 to 1s 0.01s 0.5s 40
154
Voltage reduction selection during stall
prevention operation
0, 1 1 1 30
155
RT signal reflection time selection 0, 10 1 0 40
156
Stall prevention operation selection 0 to 31, 100, 101 1 0 30
157
OL signal output timer 0 to 25s, 9999 0.1s 0s 30
158
AM terminal function selection
1 to 3, 5, 6, 8 to 14, 17, 21,
24, 50, 52, 53
1 1 32
159
Automatic switchover ON range
between commercial power-supply and
inverter operation
0 to 10Hz, 9999 0.01Hz 9999 39
160
User group read selection 0, 1, 9999 1 9999 40
161
Frequency setting/key lock operation
selection
0, 1, 10, 11 1 0 41
Automatic
restart
functions
162
Automatic restart after instantaneous
power failure selection
0, 1, 10, 11 1 0 33
163
First cushion time for restart 0 to 20s 0.1s 0s 33
164
First cushion voltage for restart 0 to 100% 0.1% 0% 33
165
Stall prevention operation level for
restart
0 to 150% 0.1% 120% 33
Current
detection
166
Output current detection signal retention
time
0 to 10s, 9999 0.1s 0.1s 40
167
Output current detection operation
selection
0, 1 1 0 40
168
Parameter for manufacturer setting. Do not set.
169
Cumulative
monitor
clear
170
Cumulative power meter clear 0, 10, 9999 1 9999 32
171
Operation hour meter clear 0, 9999 1 9999 32
User
group
172
User group registered display/batch
clear
9999, (0 to 16) 1 0 40
173
User group registration 0 to 999, 9999 1 9999 40
174
User group clear 0 to 999, 9999 1 9999 40
Function
Parameters
Name Setting Range Increments Initial Value
Refer to
page