25
Input terminal function assignment
178
STF terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 60, 62, 64 to 67,
9999
1 60 41
179
STR terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 61, 62, 64 to 67,
9999
1 61 41
180
RL terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 62, 64 to 67, 9999
1 0 41
181
RM terminal function selection 1 1 41
182
RH terminal function selection 1 2 41
183
RT terminal function selection 1 3 41
184
AU terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 62 to 67, 9999
1 4 41
185
JOG terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 62, 64 to 67, 9999
1 5 41
186
CS terminal function selection 1 6 41
187
MRS terminal function selection 1 24 41
188
STOP terminal function selection 1 25 41
189
RES terminal function selection 1 62 41
Output terminal
function assignment
190
RUN terminal function selection
0 to 5, 7, 8, 10 to 19, 25,
26, 45 to 47, 64, 70, 90 to
96, 98, 99, 100 to 105,
107, 108, 110 to 116, 125,
126, 145 to 147, 164, 170,
190 to 196, 198, 199, 9999
1 0 41
191
SU terminal function selection 1 1 41
192
IPF terminal function selection 1 2 41
193
OL terminal function selection 1 3 41
194
FU terminal function selection 1 4 41
195
ABC1 terminal function selection
0 to 5, 7, 8, 10 to 19, 25,
26, 45 to 47, 64, 70, 90,
91, 94 to 96, 98, 99, 100 to
105, 107, 108, 110 to 116,
125, 126, 145 to 147, 164,
170, 190, 191, 194 to 196,
198, 199, 9999
1 99 41
196
ABC2 terminal function selection 1 9999 41
Multi-speed
setting
232 to 239
Multi-speed setting 8 speed to 15 speed 0 to 400Hz, 9999 0.01Hz 9999 28
240
Soft-PWM operation selection 0, 1 1 1 35
241
Analog input display unit switchover 0, 1 1 0 39
242
Terminal 1 added compensation amount
(terminal 2)
0 to 100% 0.1% 100% 35
243
Terminal 1 added compensation amount
(terminal 4)
0 to 100% 0.1% 75% 35
244
Cooling fan operation selection 0, 1 1 1 42
Slip
compensation
245
Rated slip 0 to 50%, 9999 0.01% 9999 42
246
Slip compensation time constant 0.01 to 10s 0.01s 0.5s 42
247
Constant-output region slip
compensation selection
0, 9999 1 9999 42
250
Stop selection
0 to 100s, 1000 to 1100s,
8888, 9999
0.1s 9999 42
251
Output phase failure protection
selection
0, 1 1 1 42
Frequency
compensation
function
252
Override bias 0 to 200% 0.1% 50% 35
253
Override gain 0 to 200% 0.1% 150% 35
Life check
255
Life alarm status display (0 to 15) 1 0 42
256
Inrush current limit circuit life display (0 to 100%) 1% 100% 42
257
Control circuit capacitor life display (0 to 100%) 1% 100% 42
258
Main circuit capacitor life display (0 to 100%) 1% 100% 42
259
Main circuit capacitor life measuring 0, 1 1 0 42
260
PWM frequency automatic switchover 0, 1 1 1 35
Function
Parameters
Name Setting Range Increments Initial Value
Refer to
page